Function library

Function blocks

3.5.5

Analog inputs via terminal X6/1, X6/2 and X6/3, X6/4 (AIN)

3−102

l

EDSVS9332P−EXT DE 2.0

3.5.5

Analog inputs via terminal X6/1, X6/2 and X6/3, X6/4 (AIN)

Purpose

These function blocks are the interface for analog signals as the

l

setpoint input,

l

actual value input and

l

parameter control.

C0034

1
2

AIN1

+
+

AIN1-OUT

AIN1-GAIN

AIN1-OFFSET

C0404/1

C0404/2

C0402

C0403

C0400

Fig. 3−47

Analog input via terminal X6/1, X6/2 (AIN1)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

AIN1−OFFSET

a

C0404/1

dec [%]

C0402

1

19502

AIN1−GAIN

a

C0404/2

dec [%]

C0403

1

19504

AIN1−OUT

a

C0400

Special features of AIN1

l

A dead band element can be integrated into the output signal at AIN1 via code C0034.
Together with the jumper position X2 (controller front) the function 4 ... 20 mA can be
implemented as a master current value.

l

The signal is read cyclically (1 ms).

3
4

AIN2

+
+

AIN2-OUT

AIN2-GAIN

AIN2-OFFSET

C0409/1

C0409/2

C0407

C0408

C0405

Fig. 3−48

Analog input via terminal X6/3, X6/4 (AIN2)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

AIN2−OFFSET

a

C0409/1

dec [%]

C0407

1

19503

AIN2−GAIN

a

C0409/2

dec [%]

C0408

1

19505

AIN2−OUT

a

C0405

Special feature of AIN2

l

The signal is read cyclically every 250

ms.