Filter time constant, Function library, Function blocks – Lenze EVS9332xP User Manual

Page 285

Advertising
background image

Function library

Function blocks

3.5.59

Switching points (SP)

3−257

l

EDSVS9332P−EXT DE 2.0

Negative dead time

I N x - 1

I N x - 2

S P 2 - L - I N

S P 2 - S T A T x

H I G H

L O W

T

d e a d

T

d e a d

T r a v e l d i r e c t i o n

( n e g a t i v e d e a d t i m e )

Fig. 3−206

Function of the negative dead time

l

With a negative dead time, the drive reacts later by the time period set.

3.5.59.4

Filter time constant

This function is available only for the FB SP2.

Purpose

Avoids undefined switching of the output signals at SP2−STAT1 ... SP2−STAT4 when the motor is
running at low speed.

Function

l

The filter time constant is entered via C1659.

– The setting is valid for SP2−STAT1 ... SP2−STAT4.

Assignment of the codes to the filter time constant:

Code

Value

Filter time constant

C1659

0

Off

1

1 ms

2

2 ms

4

4 ms

8

8 ms

16

16 ms

Tip!

The correct setting can only be found by testing.

In general:

l

The lower the resolution of the actual position encoder and the lower the travel speed, the
higher the filter time constant.