Function library

Function blocks

3.5.8

Analog output via terminal 62/63 (AOUT)

3−109

l

EDSVS9332P−EXT DE 2.0

Example for an output value

AOUT1−IN = 50%, AOUT1−GAIN = 100%, AOUT1−OFFSET = 10%

Output terminal 62 = ((50% * 100% = 50%) + 10% = 60%) = 6 V

AOUT−GAIN

AOUT−IN

OUT

ООООО

AOUT−OFFSET

Fig. 3−60

Offset and gain of the analog output