Correction value of the phase controller, Fault indications, Oller (sync correct) (chapter 3.5.62.5) – Lenze EVS9332xP User Manual

Page 294: Fault indications (chapter 3.5.62.6), Function library, Function blocks

Advertising
background image

Function library

Function blocks

3.5.62

Multi−axis synchronisation (SYNC1)

3−266

l

EDSVS9332P−EXT DE 2.0

3.5.62.5

Correction value of the phase controller

Code

Value

Function

C0363

1 ... 5

·

Correction values for C0363 =
1

® 0.8 ms

2

® 1.6 ms

3

® 2.4 ms

4

® 3.2 ms

5

® 4.0 ms

·

C1120 = 1

– The value is automatically derived from the internal parameters of the system bus (CAN).

·

C1120 = 2

– Optimising the rise time of the phase controller depending on the frequency of the sync signal.
– Increase the value if the frequency of the sync signal decreases.
– A stable signal at SYNC1−STAT is an indicator for an optimal parameter setting.

3.5.62.6

Fault indications

Fault indications for the synchronisation via system bus

Fault

Cause

Remedy

P16

Controller was enabled in an unsynchronised
state (SYNC1−STAT = LOW)

Only enable the controller when SYNC1−STAT = HIGH

The time between two sync telegrams is
faulty

C0362 indicates the time between two sync telegrams

·

Set the time in C1121/1 to the time in C0362

·

Adapt the time interval of the sync telegram from the master

Fault indications for the synchronisation via terminal

Fault

Cause

Remedy

P16

Controller was enabled in an unsynchronised
state (SYNC1−STAT = LOW)

Only enable the controller when SYNC1−STAT = HIGH

Sync signal is missing

Connect sync signal with terminal X5/E5

The period of the sync signal is not a multiple
of 1 ms

Adapt the period

Sync window is too small

Adapt C1123/2 to the conditions