Function library

Working with function blocks

3.1.3

Connecting function blocks

3−10

l

EDSVS9332P−EXT DE 2.0

Create connections

1. Determine the signal source for ARIT2−IN1:

– Change to the code level using the arrow keys

– Select C0601/1 using

z or y.

– Change to the parameter level using PRG.

– Select output AIN2−OUT (selection number 55) using

z or y.

– Confirm using SH + PRG

– Change to the code level again using PRG.

2. Determine signal source for ARIT2−IN2:

– Select C0601/2 using

z.

– Change to the parameter level using PRG.

– Select output AIN2−OUT (selection number 55) using

z or y.

– Confirm using SH + PRG

– Change to the code level again using PRG.

3. Parameterise ARIT2:

– Select C0600 using

y.

– Change to the parameter level using PRG.

– Select multiplication (selection number 3).

– Confirm using SH + PRG

– Change to the code level again using PRG.

4. Determine signal source for AOUT1:

– Select C0431 using

y.

– Change to the parameter level using PRG.

– Select output ARIT2−OUT (selection number 5505).

– Confirm using SH + PRG

– Change to the code level again using PRG.

5. Enter function block ARIT2 in the processing table:

– Select C0465 and subcode 8 using

z.

– Change to the parameter level using PRG.

– Enter function block ARIT2 (selection number 5505).

– Confirm using SH + PRG

– Change to the code level again using PRG.

– The sequence of the FB processing is thus determined.