Configuration, Change of the terminal assignment – Lenze EVS9332xP User Manual

Page 25

Advertising
background image

Configuration

Change of the terminal assignment

2.4.1

Freely assignable digital inputs

2−13

l

EDSVS9332P−EXT DE 2.0

Example:
Menu "Terminal I/O; DIGIN" (terminal I/O; digital inputs)

Here are the most important aims for digital inputs

Valid for the basic configuration C0005 = 1000.

Code

controlled by

Note

CFG

Subcode

Signal name

Signal (interface)

Selection list 2

C0885

000

R/L/Q−R

DIGIN1

(Term. X5/E1)

0051

HIGH = do not invert main setpoint (CW rotation)

C0886

000

R/L/Q−L

DIGIN2

(Term. X5/E2)

0052

HIGH = Invert main setpoint (CCW rotation)

C0787

001

NSET−JOG*1

DIGIN3

(Term. X5/E3)

0053

HIGH = Main setpoint is substituted by the fixed speed from
C0039/x
The signals are binary coded.

002

NSET−JOG*2

FIXED0

1000

003

NSET−JOG*4

FIXED0

1000

004

NSET−JOG*8

FIXED0

1000

C0788

001

NSET−TI*1

FIXED0

1000

Additional acceleration and deceleration times from C0101/x
and C0103/x
The signals are binary coded.

002

NSET−TI*2

FIXED0

1000

003

NSET−TI*4

FIXED0

1000

004

NSET−TI*8

FIXED0

1000

C0880

001

DCTRL−PAR*1

FIXED0

1000

Parameter set selection:
The signals are binary coded.

002

DCTRL−PAR*2

FIXED0

1000

C0881

000

DCTRL−PAR−LOAD

FIXED0

1000

Signal LOW−HIGH loads selected parameter set with
DCTRL−PAR*x

C0871

000

DCTRL−TRIP−SET

DIGIN4

(Term. X5/E4)

0054

LOW = Controller sets TRIP (EEr)

C0876

DCTRL−TRIP−RES

DIGIN5

(Term. X5/E5)

0055

Signal LOW−HIGH = Resets active trip

C0920

000

REF−ON

FIXED0

1000

HIGH = Start homing

C0921

000

REF−MARK

FIXED0

1000

LOW−HIGH edge = Stop homing

1. Select the input of the function blocks which is to be assigned to a new source under the

configuration code CFG in the code level.

– Example:

C0787/2 (CFG/subcode) determines the source for the input "NSET−JOG*2" (signal name) in
the function block "Speed setpoint conditioning" (NSET).

2. Change to the parameter level with PRG. Select the source (signal) from the indicated list. Ask

yourself: Where does the signal for controlling this input is to come from?

– Example:

"NSET−JOG*2" is to be controlled by terminal X5/E5 (interface).

– For this, select DIGIN5 (signal) and confirm with SHIFT + PRG.

3. Change to the code level with 2 * .

4. Determine the polarity of the input terminals X5/E1 to X5/E5 (HIGH active or LOW active)

under code C0114 and subcode.

– In the code level the terminal is selected via subcode.

– Change to the parameter level using PRG and select the polarity.

– Change to the code level by 2 * PRG.

5. Repeat steps 1. to 4. until all inputs required are assigned.

6. Remove undesired connections (see chapter 3.1.3). The connection so far of the terminal

X5/E5 is not cancelled automatically. If the connection is to be cancelled:

– Select C0876 in the code level (previous target of terminal X5/E5)

– Change to the parameter level using PRG.

– Select FIXED0 (signal) and acknowledge with SHIFT+PRG.