Cancel" function, Reset" function, Function library – Lenze EVS9332xP User Manual

Page 150: Function blocks

Advertising
background image

Function library

Function blocks

3.5.12

BCD decade switch (BCD)

3−122

l

EDSVS9332P−EXT DE 2.0

3.5.12.3

"CANCEL" function

The identification for "CANCEL" at the inputs BCDx−DATAx results in the following state:

Input/output

Signal

Function

BCDx−EOT

HIGH

Switches

BCDx−NEW−DATA

HIGH

Switches

Sets BCDs which are not yet read to zero and stops reading.

The inputs BCDx−DATAx expect the sign as the next BCD.

3.5.12.4

"RESET" function

The identification for "RESET" at the inputs BCDx−DATAx results in the following state:

Function

Input/output

Signal

Switches

BCDx−EOT

LOW

Switches

BCDx−DATA−FLT

LOW

Switches for a millisecond

BCDx−NEW−DATA

LOW

Switches if BCDx−FAIL−IN = LOW is switched at the same time (internal OR link).

BCDx−FAIL

LOW

Switches if BCDx−BUSY−IN = LOW is switched at the same time (internal OR link).

BCDx−BUSY

LOW

The inputs BCDx−DATAx expect the sign as the next BCD.

The BCD read last remains and can be transmitted to the target code.