3.5.29

Digital frequency ramp function generator (DFRFG)

3−175

l

EDSVS9332P−EXT DE 2.0

3.5.29.6

Start via touch probe initiator (terminal X5/E5)

Stop!

In the default setting the terminal X5/E5 is assigned to another function.

Function

l

Set C0757 = 1.

l

The function is activated by simultaneously setting the inputs:

– DFRFG−QSP and DFRFG−RESET = HIGH.

l

Starting procedure:

– Signals at DFRFG−QSP and DFRFG−RESET = LOW.

– Otherwise touch probe signals are ignored.

l

A LOW−HIGH edge at terminal X5/E5 starts the process:

t

DFRFG-RESET

DFRFG-QSP

Touch-Probe X5/E5

DFRFG-OUT

DFRFG-IN

Fig. 3−128

Start via touch probe initiator (terminal X5/E5)