7Ć12

7.6

Constructing Long Cable Segments

To construct a cable segment longer than the standard maximum

cable spool length (over 1,000 feet or 300 m for Belden 9259 and

over 2,000 feet or 600 m for Belden 8213), use a BNC jackĆtoĆjack

inĆline splicing adapter. Use the following procedure to construct a

long cable segment:
Step 1.

Terminate both parts of a cable segment.

Step 2.

Splice both parts using the jackĆtoĆjack adapter. (Refer to

figure 7.20.) Ensure that the splicing connection can be

accessed easily.

ADAPTER

CONNECTOR

MATED

CABLE

ASSEMBLY

COMPLETED

INSTALLATION

BOOT

CONNECTOR

Figure 7.20 Ć Cable Splicing

Step 3.

Isolate the splicing connection with an insulating jacket, a

boot, heat shrink tubing, or electrical sealant tape.

Step 4.

Document this connection on the cable system layout.