Use the following procedure to isolate the cause of a

communication failure:
Step 1.

Verify that the drop number of the slave modules is

unique and the drop number is set correctly via the

Change Drop command.

Step 2.

Verify that drop depth has been specified. If you have

performed the self test function, the module will power up

with a drop depth of 0". If the Network module is used in

an AutoMax Version 1.0 system or a DCS 5000 system, it

will also power up with a drop depth of 0". Writing a valid

drop depth to register 20 or running an application task

that defines drop depth will clear this error.

Step 3.

Verify that the drop depth specifications for each slave

module are such that the slave modules do not overlap in

drop numbers. Only one slave module can be configured

to respond to any given drop number.
NOTE: Use steps 4 through 8 below if you have a coaxial

cable network. If you have a fiberĆoptic network, see

chapter 21.

Step 4.

Verify that the network connections to each module are

secure. Check the drop cable connection at the module

faceplate and at the passive tap. Verify that the coax

cable connections are secure.

Step 5.

Verify that the network cabling is terminated correctly.

There must be a line terminator at each end of the

network.

Step 6.

Verify that the cabling between Network modules is

installed in its own separate conduit held free from major

noise sources, such as power or other signal wires.

Step 7.

Inspect and test the cable system following the

instructions in sections 3.5.1 and 3.5.4.

Step 8.

Verify that the network cabling does not exceed the

maximum allowable length given the number of physical

drops and its electrical characteristics.

19.2.3

Interpreting AĆB Remote I/O Error Codes

You can view the AĆB Remote I/O error codes by using any of the

following:
D Processor Info. screen
D monitoring register 2002, the AllenĆBradley Remote I/O Error

Code, of the PC3000 Application Interface

Use the following table to help you interpret the AĆB Remote I/O

Interface error codes: