Configuring BlockĆTransfers

For each blockĆtransfer request you will be sending, you must

assign variable names to the following before you can send a

blockĆtransfer request:
D status and control registers in which you specify the destination

and behavior of the request

D data table registers, which are used to exchange data between

the scanner module and the blockĆtransfer module

14.2.1

Assigning Variable Names to a BlockĆTransfer

Status and Request Table

Each blockĆtransfer request has 4 words reserved for status and

control. The words are organized as follows:

This word:

Is used to:

Status and Control (first word)

initiate the request and monitor its

status
This is the blockĆtransfer status and

control register.

Rack/Slot/Grp/Req (second word)

D define the blockĆtransfer module's

location

D define the request as either a read or

a write

Length of Block Xfer (third word)

define the number of words read or

written during the transfer

Update Time (fourth word)

specify how often you want the request

to be initiated

See Appendix D, Register Assignment Map" for a listing of the

registers associated with the blockĆtransfer status and request table.
To assign variable names to the blockĆtransfer status and request

table registers, use the scanner module's Variable Configurator

form. When you choose the Block Transfer Status and Request

Table view, you see a form similar to the one shown in figure 14.3.