11Ć3

Note: If you do not enable bit 15 (hardware handshaking) in the

SETUP parameter of the OPEN statement, only pins 2, 3, and 5 of the

port you OPEN are functional.

Pin Number I/O

RSĆ232 Function

2

I

Received data

3

O

Transmitted data

4

O

Receiver status
The signal is true whenever the receiver can

accept characters, i.e., when the receiver buffer

is not full. When the receiver buffer fills to within

53 characters, the signal is turned off. The signal

can be used to disable another transmitter. It

applies when hardware handshaking is enabled.

5

ground Signal ground

6

I

Receiver enabled
This signal must be true for the receiver to

accept characters. If the signal becomes false

while a message is being received, characters

being received are deleted and an error is

reported to the application software. This signal

applies when hardware handshaking is enabled.

7

O

Transmitter status
The signal is true whenever the transmitter is

sending characters. It is used to bracket" a

character transmission. It can be used to

enable/disable any type of external equipment,

such as a triĆstate transmit modem, which

requires an enable signal to output characters.

Refer to the OPEN statement in the BASIC

Language instruction manual for details about

the operation of the Modem Enable signal

(RTS).

8

I

Transmitter enable
The signal must be true for the transmitter to

send a character. This signal is typically used for

hardware flow control when hardware

handshaking has been enabled.

Use the following table to help you make the cable you need.

ББББББББББББББ

For an example of this cable configuration:

БББББББ

See:

ББББББББББББББ

ББББББББББББББ

modem transmit enable with no flow control

БББББББ

БББББББ

Figure 11.2

ББББББББББББББ

ББББББББББББББ

cable break detect

БББББББ

БББББББ

Figure 11.3

ББББББББББББББ

ББББББББББББББ

oneĆdirectional flow control

БББББББ

БББББББ

Figure 11.4

ББББББББББББББ

ББББББББББББББ

biĆdirectional flow control

БББББББ

БББББББ

Figure 11.5

ББББББББББББББ

ББББББББББББББ

RSĆ422 cable

БББББББ

БББББББ

Figure 11.6

Advertising