14Ć9

14.3.5

Initiating BlockĆTransfer Requests to I/O Modules

A blockĆtransfer request must be initiated before it can execute. To

initiate a blockĆtransfer request, set bit 0 of the variable associated

with the request's Initiate Block Xfer register to 1 (on). For example,

to initiate blockĆtransfer request 1, set bit 0 of register 832 to 1 (on).

For this type of blockĆtransfer:

The Initiate Block Xfer bit:

continuous

remains set until an error occurs

nonĆcontinuous

remains set until the request has been

completed or an error occurs

You can stop a request by resetting the Block Xfer bit to 0 (off).
You can determine when the blockĆtransfer request is completed by

monitoring the Block Xfer Complete bit (bit 9 in the Status and

Control word). For more information, see section 14.4.
Before initiating a blockĆtransfer write request, make sure to place

the data you want to write to the target module within the request's

data table. Place the data starting at word 0. Place as much data as

you specified in the length of the blockĆtransfer.

14.3.6

Using the BlockĆTransfer Data Table

The blockĆtransfer data table is the storage location for data being

written to and read from the target blockĆtransfer modules. You must

create logic that places data in the appropriate data table words for

transfer to the module and for extracting the data received from the

module. The amount of data in the data table should correspond to

the number of words being transferred (length of the blockĆtransfer).

14.4

Monitoring BlockĆTransfer Status

WARNING

YOU MUST INCLUDE LOGIC IN YOUR APPLICATION PROGRAM TO MONITOR

THE STATUS OF EACH BLOCKĆTRANSFER REQUEST. WHEN AN ERROR

OCCURS, AN ERROR BIT IS SET, BUT YOUR APPLICATION PROGRAM MUST

READ THIS BIT SO THAT YOU WILL BE NOTIFIED OF ANY ERRORS. FAILURE TO

OBSERVE THIS PRECAUTION COULD RESULT IN UNPREDICTABLE MACHINE

OPERATION AND BODILY INJURY.