Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 50

Advertising
background image

3Ć12

Coaxial

Cable

Protection

The coaxial cable must be properly handled prior to and during

installation. Improper handling may result in cable damage and

require cable replacement. Use the following guidelines when

handling the coaxial cable:
D Keep the cable ends tightly sealed (e.g., with cable caps)

during storage, transportation, and installation of the cable.

Keeping the cable ends sealed helps prevent exposure to

moisture or other foreign matter.

D Do not exceed the minimum bend radius of the cable during

storage or installation. Refer to Appendix C for cable

specifications. Bending the coaxial cable sharper than the

recommended minimum bend radius may decrease the

reliability of the network.

D Prevent the cable from contacting abrasive surfaces such as

concrete.

D Follow the cable pulling recommendations specified in

section 7.3.

Electrical

Isolation

Use the following guidelines when installing the coaxial cable to

ensure electrical isolation:
D The exposed metal parts of the AutoMax network cable

system components (BNC connectors, adapters,

terminating loads) must not come in direct contact with

electrical conductors (including electrical enclosures,

AutoMax racks, tap shells, conduits, etc.). If necessary,

shield these components using insulating jackets, heat

shrink tubing, or electrical seal tape.

D The network coaxial cable must be installed in a separate

metal conduit. This conduit must be properly grounded

along the entire length.

D The network coaxial cable must not be installed closer than

1 m (three feet) away from electrical motors, generators,

transformers, arc welders, rectifiers, high voltage lines,

induction heat sources, and sources of microwave radiation.

D If grouping the network coaxial cable with other cables and

you cannot avoid wires, you must comply with the

recommendations provided in the ANSI/IEEE Standard

518Ć1982.

D Grounding, lightning, and surge protection of the network

cable system and attached equipment must comply with the

requirements of applicable codes.