Remote Rack Status (8 words per rack)

Register:

Bit:

Function:

Access:

Rack 35

744Ć751

Rack 35 Rack Status

and Control

See

layout for

rack 0.

Rack 36

752Ć759

Rack 36 Rack Status

and Control

See

layout for

rack 0.

Rack 37

760Ć767

Rack 37 Rack Status

and Control

See

layout for

rack 0.

Scanner

Register:

Bit:

Function:

Access:

Scanner Control

768

Defines the scan mode and

enables scanning

read/write

0

Scanner mode
To place the scanner in RUN

mode, set this bit to 1.
To remove the scanner from

RUN mode, reset this bit to 0.

1

To start the scanner scanning

remote I/O, set this bit to 1.
To stop the scanner from

scanning remote I/O, reset

this bit to 0.

Data Rate

769

Sets the communication rate

for the scanner
For a communication rate of

57.6 kbps, write a value of 0

into this register.
For a communication rate of

115.2 kbps, write a value of 1

into this register.
For a communication rate of

230.4 kbps, write a value of 2

into this register.

read/write

Remote I/O Link

Status

770

0

When this bit is set to 1, the

scanner is receiving

communication from all

enabled racks.
When this bit is 0, one or

more remote racks have an

error.

read

Module

Identification

771

Contains the module

identification number, which is

43525 (0xaa04 hex) unsigned

or -22012 signed. The

signed value is displayed by

the AutoMax Programming

Executive software.

read

Not Used

772Ć775

Not used