Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 189

Advertising
background image

18Ć7

Registers

Description

Register 19 Ć

Messages

Transmitted

This register reflects the total number of messages

transmitted by the module. While the line is inactive, this

value will remain unchanged in the slave. In the master,

this value will rapidly increase as initialization request

messages are constantly being sent. While the line is

active, this value will constantly increase to 65535 and

then roll over to zero.

Register 20

(Drop Depth)

In the master, this register is not used. In the slave, this

register is used to define the number of drops that

particular slave module represents. The drop depth

register must never be set to a value less than 1 or greater

than 56 minus the drop setting. In other words, if the drop

setting is 54, the drop depth cannot be set greater than 2.

Likewise, if the drop setting is 10, the drop depth cannot

be set greater than 46.
The drop depth should be set to the minimum value

required to satisfy the application to minimize the update

period for that module. The drop depth value can be

modified at any time without removing an active drop from

the network. Note that the assignment of physical or

virtual drops must not overlap or transmission collisions

will occur.
Bit 14 of this register is the error bit. It is set by the

Network module if the existing drop depth value is invalid.

When bit 14 is set, the last valid drop depth value is used.

An invalid drop depth value written by an application task

should be discovered and corrected during initial system

testing.
Bit 15 is the processing complete bit. It is set when the

Network module has completed processing of the drop

depth register. If the drop depth value is changed by an

application task, the task must monitor bit 15 to verify that

the drop depth value processing has been completed by

the Network module.
To assign drop depth, an application task writes the

desired integer value to this register. The processing

complete bit (bit 15) and the error bit (bit 14) should then

be monitored to verify that the drop depth value has been

accepted and processed. The application task must

ensure that the processing complete bit is equal to 1 and

the error bit is equal to 0 before proceeding.

Advertising
This manual is related to the following products: