BĆ1

Appendix B

Recommendations for Building

CEĆCompliant Systems

This appendix provides instructions about how to build and install an AutoMax

PC3000 system compliant with the European Union Directives 89/336/EEC,

Electromagnetic Compatibility (EMC), and 73/23/EEC, Low Voltage

requirements.
These instructions are only applicable to the industrial environment as it is

defined in the standards accompanying these Directives.

AutoMax PC3000 Packaged Version (M/N 57C570)

The requirements for an AutoMax PC3000 Packaged Version installation

compliant with the European Union EMC and Low Voltage Directives are:
1. Install the AutoMax PC3000 Packaged Version inside a grounded cabinet.
2. Provide incoming power to the AutoMax PC3000 Packaged Version via a

control transformer. The recommended transformer rating is 0.5 KVA

minimum.

3. Install an EMI/RFI filter between the AutoMax PC3000 Packaged Version and

the control transformer. The Corcom 10VV1 filter (Reliance Electric P/N

612421Ć1) is recommended for both 120 V and 220 V AC. Install the filter as

close to the PC3000 chassis as possible. Connect the filter input to the

control transformer with a shielded cable or twistedĆpair wires of the

appropriate size. If a shielded cable is used, ground the shield at one end.

Connect the filter output to the PC3000 chassis with a shielded cable or

twistedĆpair wires of the appropriate size. Make sure that the wires

connecting the control transformer with the filter input are as far away as

possible from the wires that connect the filter output with the PC3000.

Ground the filter case.

4. Install a surge protection device between the EMI/RFI filter and the control

transformer. The RAVĆ401BWZĆ2A surge protector from Okaya Electric

Industries Co., LTD (Reliance Electric part number 600686Ć44A) is

recommended for a line voltage of 120 V AC. The RAVĆ781BWZĆ2A surge

protector from Okaya Electric Industries Co., LTD (Reliance Electric part

number 600686Ć44B) is recommended for a line voltage of 220 V AC.
If the control transformer secondary is grounded, one surge protector is

required. The surge protector has three wires, labeled terminal 1, ground,

and terminal 2. Connect the surge protector wire labeled 1 or 2 to the filter

input terminal, which is connected to the ungrounded end of the control

transformer secondary. Connect the surge protector's ground wire to the

filter input terminal, which is connected to the ungrounded end of the control

transformer secondary. Make these wires as short as possible. See figure

B.1.