Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 115

Advertising
background image

8Ć3

1

2

3

4

5

6

DATA Ć DROP CABLE BROWN WIRE

DATA Ć DROP CABLE BROWN/WHITE WIRE

120ĆOHM LOAD JUMPER*

120ĆOHM LOAD JUMPER*

+24 V DC

GROUND (Connected to transceiver enclosure)

*A jumper between terminals 3 and 4 connects an internal 120Ćohm terĆ

mination resistor between terminals 1 and 2. This jumper must be used

on all StandĆAlone Transceivers.

TRANSCEIVER

TERMINAL

CONNECTION

Figure 8.2 Ć StandĆAlone Transceiver Terminal Block Connections

Step 4.

Connect the transceiver to the fiberĆoptic network using

the guidelines provided in section 8.5.

Step 5.

Turn power on to the transceiver.

8.2

Installing the Rack/Power Supply and

RackĆMounted Transceivers

You must make sure the rack is installed in an electrical cabinet.

Ensure that all cables are long enough to provide accessibility to the

RackĆMounted Transceivers from the back of the rack to aid in

replacement or troubleshooting. Use the following procedure to

install the Rack/Power Supply and RackĆMounted Transceivers.
Step 1.

Set the selector switch on the back of the rack to 115 or

230 V AC as required.

Step 2.

Install the rack using #8 screws. Allow at least 2.5Ć5 cm

(1Ć2 in.) clearance around the rack for adequate

ventilation. Rack mounting dimensions are shown in

figure 8.3.