About the PC3000 Processor Functionality

The PC3000 Processor has 370K of RAM available for application

programs. It can run programs created using AutoMax Enhanced

BASIC, Enhanced Ladder Language, or Control Block languages.

The Processor supports the AutoMax multiĆtasking environment.

1.2.2

About the AĆB Remote I/O Functionality

Use the AllenĆBradley Remote I/O Scanner interface to link the

PC3000 to AllenĆBradley I/O devices that communicate via the

remote I/O link. The scanner interface can control such devices as

AllenĆBradley's 1771 I/O, Flex I/O, Block I/O, SLC 500 Remote I/O

Adapter Module and companion I/O modules, and operator

interfaces. The scanner interface can scan both discrete and analog

I/O as well as force inputs and outputs.
The scanner interface supports 1Ć, 2Ć, and 1/2Ćslot addressing of a

maximum of 32 remote racks. These racks can be either 1/4, 1/2,

3/4, or full racks. The PC3000 supports remote I/O communication

rates of 57.6, 115.2, and 230.4 Kbps and can send a maximum of 48

blockĆtransfer read or write requests of up to (and including) 64

words each.

About How the Scanner Module Transfers Discrete Data
A shared memory interface allows the scanner interface to

communicate to the remote I/O adapter devices. It exchanges

discrete data with remote I/O adapters. Figure 1.3 illustrates how

discrete data is transferred.

Adapter

Adapter

Adapter

Rack 3

Rack 2

Rack 1

Data Exchange

Shared

Memory

Interface

Program

Scan Loop

Remote I/O

Scan Loop

Program

Figure 1.3 Ć Discrete Data Transfer