2 dividing i/o into racks – Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 61

Advertising
background image

4Ć3

4.2

Dividing I/O into Racks

I/O modules are installed in a chassis, but you must group the I/O

points logically into an I/O rack, which is the principal I/O addressing

unit. An I/O rack is composed of 128 inputs and 128 outputs or 8

input words and 8 output words.
Use this section to help you divide your I/O points into racks. This

section describes:
D AllenĆBradley's I/O addressing concept
D how to address blockĆtransfer modules
D how to determine your remote I/O racks

4.2.1

AllenĆBradley's I/O Addressing Concept

Since the purpose of the PC3000 Remote I/O scanner is to read

inputs and control outputs of field devices such as switches, valves,

and thermocouples, these inputs and outputs must occupy a

location in the scanner module's memory so that they can be

addressed in your control program. Each terminal on an input or

output module that can be wired to a field device occupies a bit

within the PC3000's memory. The part of memory that houses I/O

addresses is the input image table and the output image table.
I/O addressing maps the physical location of an I/O module terminal

to a bit location in the PC3000's memory. I/O addressing is a

method of segmenting the PC3000's memory. See Table 4.1 for

information about how memory is mapped into an I/O address.

Advertising
This manual is related to the following products: