For example, if the target module for request 1 was

located in I/O group 3, bits 9Ć11 of register 833 should

contain the value of 3.

833:

xxxx 0110 xxx0 0111

14.3.2

Specifying a Read or Write Operation

You must define a blockĆtransfer request to be either a read or a

write request. To do this, set bit 15 of the variable associated with

the second word within the request's status and control table, which

is labeled Rack/Slot/Group/Req.

To specify this type of reĆ

quest:

Set bit 15 of the variable associated with the

request's Rack/Slot/Group/Req register to:

read

1

write

0

For example, to specify blockĆtransfer 1 to be a read request, bit 15

of register 833 would contain a value of 1.

833:

1xxx 0110 xxx0 0111

14.3.3

Specifying the Length of a BlockĆTransfer

The length of the blockĆtransfer specifies how many words of data

will be read from or written to the target blockĆtransfer module per

blockĆtransfer request. Specify the length of the blockĆtransfer

request by loading a value of 1Ć64 into the variable associated with

the Length of Block Xfer register within the blockĆtransfer status and

control table. This parameter corresponds to the third word within

this table.
For example, if you wanted to transfer 10 words of data during

blockĆtransfer request 1, you would load a value of 10 into

register 834.

14.3.4

Specifying the Update Time of the BlockĆTransfer

Setting an update time determines if a blockĆtransfer is continuous

or nonĆcontinuous. You specify an update time for a blockĆtransfer

request within the variable associated with the register labeled

Update Time (the fourth word of the request's blockĆtransfer status

and request table). The time you enter is in intervals of 10 ms.

To specify this type of blockĆtransfer:

Enter this within the request's

Update Time register:

continuous

a value in units of 10 ms
Update time (ms) = n  10,

where n is the number you load

into the register.

nonĆcontinuous

a value of 0

For example, if you wanted blockĆtransfer request 1 to execute every

30 ms, you would place a value of 3 into register 835.
For more information about continuous and nonĆcontinuous

blockĆtransfers, see section 14.1.2.