Control Transformer

Filter

PC3000

Surge Suppressor

IN

OUT

Figure B.1 Ć Connecting a Grounded Control Transformer Secondary

If the control transformer secondary is ungrounded, two surge protectors are

required: one for the lineĆtoĆline and one for lineĆtoĆground protections. Connect

the first surge protector wire labeled terminal 1 or 2 to one of the filter input

terminals. Connect the surge protector's ground wire to the other filter input

terminal. Connect the second surge protector's wires labeled 1 and 2 to the filter

input terminals. Connect the second surge protector's ground wire to the

protective ground. Make these wires as short as possible. See figure B.2.

1

2

G

G

L

N

Control Transformer

Filter

PC3000

Surge Suppressor 2

1

2

G

not used

Surge Suppressor 1

IN

OUT

Figure B.2 Ć Connecting an Ungrounded Control Transformer Secondary