BĆ3

5. Connect the AutoMax PC3000 Packaged Version to a protective ground with

an individual ground wire. A protective ground terminal is provided on the

PC3000 chassis. It is located below the input terminal block and marked

with an appropriate international symbol. The ground wire must be selected

in accordance with appropriate international and national standards.

6. AutoMax DCSĆNET and AllenĆBradley Remote I/O cable systems must be

installed in accordance with the requirements described in their instruction

manuals.

7. RSĆ232/RSĆ422 cables connecting user devices to ports A and B on the

Serial card must be shielded. Cable connectors must have EMI/RFI shielded

cable clamps attached to the cable shield. No other measures are needed

since the cable shield is grounded at the PC3000. Cable lengths must not

exceed 10 m (33 ft.). For longer distances, use CE marked modems or

equivalent devices. Power them from the same control transformer as the

PC3000 to which they are connected.

AutoMax PC3000 Installed in a PC Chassis

For an AutoMax PC3000 installed in a PC chassis to be compliant with the

European Union EMC and Low Voltage Directives, use a CEĆmarked PC and

follow the installation instructions published in the PC's manual as well as the

instructions in points 6 and 7 above. If necessary, use a CEĆmarked

uninterruptable power supply (UPS).