0 - maintaining the dcs-net network, 1 maintaining the coaxial cable dcs-net network, 0 maintaining the dcsćnet network – Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 233: 1 maintaining the coaxial cable dcsćnet network

Advertising
background image

21Ć1

21.0 MAINTAINING THE

DCSĆNET NETWORK

21.1

Maintaining the Coaxial Cable DCSĆNET

Network

Refer to this section for information about adding or disconnecting a

network drop, maintaining the cable system design and

documenting and inspecting the cable system.

For information about:

See this section:

Maintaining the Coaxial Cable DCSĆ

NET Network

21.1

Maintaining the FiberĆOptic DCSĆNET

Network

21.2

What to Do Next

21.3

21.1.1 Adding a Network Drop

Use the following procedure to add a drop to the coaxial cable network:
Step 1.

Identify the route for a new cable segment (or segments).

Refer to the recommendations provided in chapter 3. If a

new drop is to be added at the end of the network cable

system, only one new cable segment will be necessary.

Otherwise, two new cable segments will be necessary.

Step 2.

Calculate the new cable segment length. Ensure that the

new total cable length does not exceed the maximum

cable length defined in the AutoMax network specification

(see Appendix C). If it exceeds the maximum specified

cable length, consult with Reliance Electric before taking

any further steps.

Step 3.

Cut, install, terminate, and test the new cable segment

following the instructions provided in chapter 7.

Step 4.

Stop all communications over the AutoMax network.

Step 5.

Refer to figure 21.1 and use the following procedures if a

new drop is to be added to one of the ends of the

network. Skip to step 6 if a drop is to be added along the

cable route.
a) Disconnect the terminating load from the tap of the

existing drop and replace it with one end of the new

cable segment.

b) Connect the terminating load to a new tap. Connect

the other end of the new cable segment to this tap.

c) Attach the tap to the Network module using a drop

cable.