13Ć4

For this information:

See:

listing of the registers associated with

the remote rack status and control

appendix D, Register Assignment

Map"

how to clear and correct rack errors

chapter 16, Initializing the AutoMax

PC3000 AĆB Remote I/O Scanner"

To assign variable names to the remote rack status and control

registers, use the scanner's Variable Configurator form. When you

choose the Remote Rack Status and Control Table view, you see a

form similar to the one shown in Figure 13.3.

Figure 13.3 Ć Remote Rack Status and Control Table View

All remote rack status and control registers are read only, except the

rack enable register.
For information about enabling a remote rack and monitoring its

status, see chapter 16, Initializing the AutoMax PC3000 AĆB Remote

I/O Scanner."

13.3

Configuring the I/O Scanner by Assigning

Variable Names to the Scanner Setup and

Status Registers

Registers within the scanner, which are 16Ćbit words, have been

assigned to these functions:
D controlling scanning and the scan mode
D defining the remote I/O communication rate
D monitoring the remote I/O link status
D storing the module ID
See Appendix D, Register Assignment Map" for a complete listing

of the registers associated with the scanner setup and status.