5 detecting partial network failure, 6 what to do next – Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 192

Advertising
background image

18Ć10

RESET

DROP_STATUS_

FROM_NETWORK

FAULT_STATUS

FAULT_STATUS

Figure 18.3 Ć Examining Network Status

DROP_STATUS can be either the drop 0 status bit in the slave drop

or the particular drop's status bit in the master. RESET indicates a

manual reset under operator control. When the drop goes offline for

the 120 ms period, the FAULT_STATUS coil will go high and stay

high until it is manually reset by the operator.

18.5

Detecting Partial Network Failure

Recall that all data is broadcast, i.e., transmitted simultaneously to

all drops. If a response is not received from a targeted drop, the

master will retry three times to communicate with that drop.

However, if a drop that was not targeted for that transmission did not

receive the message correctly, the master will not retransmit the

message unless the targeted drop also did not receive it. It is

possible, therefore, that this drop will not contain the most current

copy of the data.
This problem can be detected by monitoring status registers 15Ć18

in the drop 0 area of the module. If these values increase rapidly

over a short period of time, there is a problem with network integrity.
If this is a concern in your application, you should direct data from

slave to master to slave. For example, assume data from one rack

(drop 1) is critical to the operation of another rack (drop 2). After this

data is transmitted to the master, the master can transfer it to its

drop 2 area and then transmit it directly to drop 2.

18.6

What to Do Next

Refer to chapter 19 to help you troubleshoot the PC3000.

Advertising
This manual is related to the following products: