0 - connecting an allen-bradley remote i/o link, 0 connecting an allenćbradley remote i/o link – Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 121

Advertising
background image

9Ć1

9.0 CONNECTING AN

ALLENĆBRADLEY REMOTE

I/O LINK

If you are using the AutoMax PC3000 Processor card to control

AllenĆBradley remote I/O, you must connect the remote I/O link.

For informtion about:

See this section:

Connecting the Remote I/O Link to

the Processor Card

9.1

What to Do Next

9.2

9.1

Connecting the Remote I/O Link to the

PC3000 Processor Card

Once the PC3000 Processor card is properly seated and secured in

the chassis, connect the remote I/O link.
If the Processor card is an end device on the remote I/O link, you

must install an appropriatelyĆsized terminating resistor while wiring

the remote I/O cable to the Phoenix connector. The resistor prevents

the signal from being reflected from the ends of the cable. A resistor

must be installed at each end of the link. You should have

determined the resistor size for the remote I/O link in section 4.3.2.

Both resistors used to terminate the link must be sized the same.

Also, make sure that the leads are short. Leads that are too long can

cause noise reflection on the link.
To connect the remote I/O link, follow these steps:
Step 1.

Locate a proper length of Belden 9463 cable.

Step 2.

Strip off enough of the cable jacket and insulation to

expose the wire inside each of the three segments.

Step 3.

Locate a Phoenix connector. This connector is shipped

installed on the Remote I/O port on the Processor card.

Step 4.

Connect the signal conductors and shield drain wire of

the twinaxial cable onto the connector's terminals as

shown in figure 9.1.

If the Processor card is an

end device, install an

appropriatelyĆsized

terminating resistor.

Clear (line 1)
Shield (Sh)
Blue (line 2)

Phoenix Connector

(oriented as if you are looking at the card as

it faces you with the LEDs upward)

Figure 9.1 ĆConnecting the Twinaxial Cable Segments onto the Phoenix

Connector

Advertising