4 determining remote i/o scan times – Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 71

Advertising
background image

4Ć13

For proper operation, you must terminate both ends of the remote

I/O link by using external resistors. Use an 82W resistor to terminate

each end of the remote I/O link, unless you are using any of the

early devices listed in Table 4.3. If you are using any device listed in

this table, you must install a 150W resistor at each end of the remote

I/O link.
NOTE: You only can have 16 physical devices on a remote I/O link

that is terminated with 150W resistors.

Table 4.3 Ć Early Remote I/O Link Devices That Require 150

Termination Resistors

Device Type

Catalog Number Series

Adapters

1771ĆAS

All

dap e s

1771ĆASB

A only

1771ĆDCM

o y

Miscellaneous 1771ĆAF

All

Miscellaneous 1771ĆAF

All

4.4

Determining Remote I/O Scan Times

The remote I/O scan time is the time it takes for the scanner to

communicate with each device in the remote I/O system. These

factors affect the remote I/O scan time:
D link data communication rate
D number of enabled racks
D number of blockĆtransfer requests
You can determine the total remote I/O scan time in a remote I/O

system by this formula:

Total Remote I/O Scan Time = # of enabled racks



time per rack

(see Table 4.4)

The formula does not take into account the time required to

complete blockĆtransfer requests. This time can be calculated

separately. See section 4.4.2 for more information.

Advertising
This manual is related to the following products: