12.2

Converting an Existing Rack into an

AutoMax PC3000

You can convert an existing rack to an AutoMax PC3000. To do this,

follow these steps:
Step 1.

Move existing modules or add modules to create this

configuration:

БББББББ

БББББББ

In this slot number:

БББББББ

БББББББ

You must have:

ББББББББ

ББББББББ

Model Number:

БББББББ

Б

БББББ

Б

БББББББ

4

БББББББ

Б

БББББ

Б

БББББББ

any AutoMax Processor

ББББББББ

Б

ББББББ

Б

ББББББББ

M/N 57C435, M/N 57C431,

M/N 57C430

БББББББ

БББББББ

5

БББББББ

БББББББ

a Network module

ББББББББ

ББББББББ

M/N 57C404

БББББББ

БББББББ

6

БББББББ

БББББББ

an AllenĆBradley

Remote I/O module

ББББББББ

ББББББББ

M/N 57C443

БББББББ

БББББББ

7

БББББББ

БББББББ

a Generic module

ББББББББ

ББББББББ

GEN32K

Remove all other modules, or the conversion will not

occur.

Step 2.

From the System Configurator, choose Modify Info from

the Rack menu.

Step 3.

Choose PC3000 in the Slots group box.

Step 4.

Make sure that the tasks are defined to run in slot 4. To

do this, use the Modify Info command from the Task

Manager's Task Menu.

Step 5.

Generate a configuration.

12.3

Specifying the DCSĆNET Drop Number and

Drop Depth

For the AutoMax PC3000 to communicate on the DCSĆNET network,

you must set its network drop number. The drop number of all

AutoMax PC3000 network interfaces are set at the factory as 55.

Each AutoMax drop must have a unique drop number. When setting

drop numbers, space their numbering to leave gaps for additional

drops.
By setting the drop depth of an AutoMax PC3000 to a value other

than 1, you can configure the AutoMax PC3000 to function as

multiple virtual drops. Setting a drop depth of more than one

provides increased register capacity for the AutoMax PC3000,

allowing it to transmit/receive more information. Leaving gaps

between drop numbers lets you easily add virtual drops. For

example, setting the drop number of an AutoMax PC3000 to 05 and

its drop depth to 3 configures it to function as drops 05, 06, and 07.
Set the drop depth to a value of 1Ć55, but do not exceed a value that

is 56 minus the drop setting. For example, if the drop number is 54,

you cannot set the drop depth greater than 2. Likewise, if the drop

number is 10, you cannot set a drop depth greater than 46. You

should set the drop depth to the minimum value required to satisfy

the application and to minimize the update period for that module.

To avoid transmission collisions, make sure that the drop numbers

and drop depth settings of DCSĆNET interfaces on your network do

not overlap.