21Ć6

21.2.3

Replacing the FiberĆOptic Rack and Power Supply

Use the following procedure to replace the FiberĆOptic Rack and

Power Supply. Before beginning this procedure, verify that the

fiberĆoptic cable, the RackĆMounted Transceiver, and its

corresponding StandĆAlone Transceiver are labeled with the network

ID number, the network drop number, and the Network module slot

number.
Step 1.

Remove the plastic panel from the front of the FiberĆOptic

Rack.

Step 2.

Turn the FiberĆOptic Rack's Power Supply off using the

rocker switch on the Power Supply's faceplate.

Step 3.

Remove power from the Power Supply's external 115 or

230 V AC source.

Step 4.

Disconnect the Power Supply's power cord from the

external 115 or 230 V AC source.

Step 5.

Disconnect the twistedĆpair cables and fiberĆoptic cables

from each transceiver in the rack.

Step 6.

Remove the rack from the mounting surface.

Step 7.

Set the selector switch on the back of the new rack to 115

or 230 V AC as required.

Step 8.

Attach the rack to the mounting surface.

Step 9.

Insert each transceiver into the new rack and connect the

twistedĆpair cable and fiberĆoptic cable (refer to chapter

8).

Step 10. Connect the power cord to the 115 or 230 V AC source.
Step 11. Turn power on to the 115 or 230 V AC source.
Step 12. Turn the FiberĆOptic Rack's Power Supply on using the

rocker switch on the Power Supply's faceplate. The

builtĆin indicator in the switch will illuminate to indicate the

presence of power. Verify that the LEDs on all of the

RackĆMounted Transceivers in the rack are on.

Step 13. ReĆattach the plastic panel to the front of the FiberĆOptic

Rack.

21.2.4

Adding a Network Drop

Use the following procedure to add a drop to the fiberĆoptic

network:
Step 1.

Identify the route for a new fiberĆoptic link. Refer to the

recommendations provided in chapter 8.

Step 2.

Calculate the new link length. Ensure the new total cable

length does not exceed the maximum cable length

defined in Appendix C. If it exceeds the maximum

specified cable length, consult with Reliance Electric

before taking any further steps.

Step 3.

Install and test the new cable segment following the

instructions provided in chapter 8.

Step 4.

Install the new StandĆAlone Transceiver following the

instructions provided in chapter 8.

Step 5.

Stop all communications over the AutoMax network.