16.0 INITIALIZING THE AutoMax

PC3000 AĆB REMOTE I/O

SCANNER

Before the AutoMax PC3000 can begin scanning remote I/O, you

must prepare it for scanning by writing and running an initialization

program. Within this program, you must do the following in this

recommended order:
D specify the data communication rate
D enable the remote I/O racks that you want the scanner to scan
D initiate scanning
D place the scanner module in run mode
D make sure all enabled racks are communicating
The following sections describe the data registers you must include

in the initialization program. For a sample program in BASIC and

Enhanced Ladder Logic languages, see Appendix G, Examples of

Remote I/O Programs."

For information about:

See this section:

Specifying the Data Communication Rate

16.1

Specifying the Remote Racks That Will Be Scanned

16.2

Initiating Scanning

16.3

Placing the Scanner in RUN Mode

16.4

What to Do Next

16.5

16.1

Specifying the Data Communication Rate

You should have determined the data communication rate in chapter

4, Designing Control Systems That Use the AutoMax AllenĆBradley

Remote I/O Link." All devices on a remote I/O link must be:
D able to communicate at the rate you have chosen
D configured to communicate at that rate
You can configure the communication rate of AllenĆBradley remote

I/O adapters by setting a switch located on the device or on the

chassis in which the adapter resides.
To specify the PC3000's remote I/O data communication rate, you

must write a value to register 769 (Data Rate) that corresponds to

the data communication rate you want. See Table 16.1.