5 calculating the data update rate, 6 what to do next – Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 58

Advertising
background image

3Ć20

3.5

Calculating the Data Update Rate

The update rate can be calculated using the following formula:
UPDATE_TIME = (DROP_TIME X N) + NEW_DROP_TEST_TIME +

MSG_XFER_TIME
where DROP_TIME = amount of time needed for the master to

request an update and a slave to respond to the request

(2.99 ms).
N = number of slave drops (physical and virtual).
NEW_DROP_TEST_TIME = amount of time needed for the

master to poll an inactive drop and wait for its response

(2.48 ms assuming no response).
MSG_XFER_TIME = amount of time to transfer programming

terminal messages. If the master is sending a message, the

MSG_XFER_TIME is 2.09 milliseconds. If a slave is sending a

message, this time is 3.395 milliseconds.

For example, a network composed of 10 drops which is not

messaging will update each drop with a period of:
[(2.99 x 10) + 2.48] ms = 32.38 ms
The same network with slaves using messaging will update each

drop with a period of:
[(2.99 x 10) + 2.48 + 3.395] ms = 35.775 ms
The update time is not affected by how many registers are used in an

application task because all 32 input and 32 output registers are

transmitted for each active drop.

3.6

What to Do Next

Finish designing your system. For more information about the

DCSĆNET network, see chapters 7, 8, and 21, and Appendix C.

Advertising
This manual is related to the following products: