Adding the Processor Card
To add the Processor card, follow these steps:
Step 1.

In the Device Manager, doubleĆclick the PC3000 device

listing. You see the Reliance Electric AutoMax PC3000

listed. If a device conflict is present, you see this icon:

Should a device conflict exist, go to section 5.7 to

manually configure the Processor card.

Step 2.

Select the Reliance Electric AutoMax PC3000, and choose

the Properties button. You see the properties for your

PC3000 Processor card.

Step 3.

Choose the Resources tab.

Step 4.

Temporarily write down the starting and ending addresses

for the card. For example: C8000ĆC9FFF.

Step 5.

Deselect the Use automatic settings option.

Step 6.

Select the Input/Output Range.

Step 7.

Choose the Change Setting button. The Edit Input/Output

Range dialog box appears.

Step 8.

In the Edit Input/Output Range dialog box, change the

range to the next available Input/Output range by using

the Value list box. Make sure there are no device conflicts.

Step 9.

Save your changes by clicking OK; exit the PC3000

Properties dialog box by clicking OK.

Step 10. When prompted by the Creating a Forced Configuration

dialog box, click Yes.

Step 11. Close the System Properties and Control Panel.

5.4.2

Adding the PC3000 Processor Card's Address to

the SYSTEM.INI File

You must edit the SYSTEM.INI file to add a reference to the PC3000

Processor card. To edit the SYSTEM.INI file, follow these steps:
Step 1.

Using a text editor, open the SYSTEM.INI file that is

located in the directory where Windows 95 is installed.

Step 2.

Locate the section [386Enh].

Step 3.

Add the following line to the [386Enh] section:

EMMExclude=MEM1-MEM2

.

Where:

MEM1 = the starting address of the PC3000

Processor card
MEM2 = the ending address of the PC3000

Processor card

Example

: EMMExclude = C800-C9FF

NOTE: Although Windows 95 displays the address range

in five digits, you must enter the address as four digits. Do

not enter the fifth digit in the SYSTEM.INI file.

Step 4.

Add a comment to this address that documents the serial

number of the Processor card. For example:

EMMExclude = C800-C9FF //(serial number)

Step 5.

Save and close the SYSTEM.INI file.