2 configuring the remote i/o racks – Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 152

Advertising
background image

13Ć2

13.2

Configuring the Remote I/O Racks

Once you have your I/O modules laid out in chassis with adapters

and have developed your I/O system addressing, you must enter

this I/O rack information into the PC3000 remote I/O scanner

interface. Assign variable names to the applicable module registers

and/or bits using the Variable Configurator form and load data into

these locations.
Each I/O rack has an input image table and an output image table.

You use these tables to store input data and to extract output data

for the rack. You must assign variable names to each input and

output word and/or bit you use in a rack. You will then be able to

use these names in your control programs.
Also, each I/O rack has status information associated with it. The

status information can be a whole register or a bit within a register

that you can monitor to detect rack communication and errors,

among other information. You must assign a variable name to each

status item so you can incorporate the variable into your control

program.

13.2.1

Assigning Variable Names to the Inputs and

Outputs in the Remote Racks

Each I/O group in an I/O rack has two corresponding registers in the

scanner PC3000, one register for inputs and one for outputs. These

registers are 16Ćbit words.
Before the scanner can communicate with an I/O rack you must

assign a variable name to the input and output image register for

each I/O group used in the I/O rack.
See Appendix D, Register Assignment Map" for a complete listing

of the registers and bits associated with the I/O image table.
To assign variable names to the input and output image table

registers, use the Scanner's Variable Configurator form. When you

choose the Input/Output Image Table view, you see a form similar to

the one shown in figure 13.2.

Advertising
This manual is related to the following products: