0 - monitoring the automax pc3000, 1 monitoring the status of the battery, 2 monitoring status – Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 183

Advertising
background image

18Ć1

18.0 MONITORING THE

AutoMax PC3000

You must monitor the status of the AutoMax PC3000, the DCSĆNET

network and the remote I/O scanner interface.

For information about:

See this section:

Monitoring the Status of the Battery

18.1

Monitoring Status

18.2

Overview of the DCSĆNET Interface

18.3

See chapter 19 for information about troubleshooting the AutoMax

PC3000.

18.1

Monitoring the Status of the Battery

To detect whether the battery on the Processor card is weak,

monitor the Variable BATTERYSTATUS4@. See section 12.6 for

information about this variable. The battery status is also available

on the online Processor Info. screen. For more information about the

onĆboard battery, see chapter 20.

18.2

Monitoring Status

WARNING

YOU MUST INCLUDE LOGIC IN YOUR APPLICATION PROGRAM TO MONITOR

SCANNER, COMMUNICATION, AND REMOTE I/O RACK STATUS. WHEN AN

ERROR OCCURS, THE APPLICABLE ERROR BIT GOES ON, BUT YOUR

APPLICATION PROGRAM MUST READ THESE BITS SO THAT YOU WILL BE

NOTIFIED OF ANY ERRORS. FAILURE TO OBSERVE THIS PRECAUTION COULD

RESULT IN UNPREDICTABLE MACHINE OPERATION AND BODILY INJURY.

18.2.1

Monitoring Scanner Status

To determine if the scanner is in RUN mode, monitor the variable

associated with Scan Mode (register 768, bit 0). Once this bit is set

(1), it remains set unless a STOP ALL error occurs, which resets the

bit to 0.

18.2.2

Monitoring Remote I/O Link Status

To determine if all the enabled racks on the remote I/O link are

communicating properly, monitor the variable associated with the

RIO Status register (register 770, bit 0). This bit is set to 1 when all

the enabled racks are communicating. When this bit is 0, one or

more remote racks have an error.
If all the racks in your control system are enabled as part of your

application, monitoring RIO Status would give you the information

you need to determine if communication is occurring.