background image

4Ć9

2Ćslot addressing (2 I/O chassis slot = 1 I/O

group = 1 input image word and 1 output

image word = 16 input bits and 16 output bits.)

0

1

2

3

4

5

6

7

Output Image Table

Word #

0

1

2

3

4

5

6

7

Input Image Table

Word #

ЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙ

I/O Image Area
Rack x

00

15

bits

00

15

bits

Group 0

ЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙ

16Ćpoint I/O modules occupy 16 bits,

an entire word, in the image table.
Installing as a pair a 16Ćpoint input

module and a 16Ćpoint output module

efficiently uses the image table.

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

Input

Terminals

Output

Terminals

NOTE: I/O terminals and racks are

numbered in octal.

Figure 4.6 Ć An Example of Efficient I/O Image Table Use

4.2.3

Addressing BlockĆTransfer Modules

BlockĆtransfer modules occupy 8 bits in the PC3000's I/O image

table. Since all blockĆtransfer modules are bidirectional, they cannot

be used to complement either input or output modules.

To address a module

occupying:

Use the:

one I/O chassis slot

assigned I/O rack and I/O group number of the

slot in which the module resides and 0 for the I/O

group slot number
When using 1/2Ćslot addressing, use the

assigned rack number, the lowest group

number, and 0 for the I/O group slot number.

two I/O chassis slots

assigned rack number, the lowest I/O group

number, and 0 for the I/O group slot number