4Ć18

4.6.2

About Remote I/O System Grounding

Figure 4.10 illustrates the recommended grounding configuration for

a remote I/O system. For more information about properly

grounding a remote I/O system, refer to the Rockwell Automation

Industrial Automation Wiring and Grounding Guidelines, publication

1770Ć4.1.

Figure 4.10 Ć Recommended Grounding Configuration for Remote I/O Systems

4.6.3

Recommended Switch Settings

Switches are used on remote I/O chassis and adapter devices for

defining:
D the I/O rack addressing method for the chassis, which defines

how much of a slot makes up a word in the I/O image table

D the state of the outputs in the chassis after a communication fault
D how the chassis can be reset
D the remote I/O link communication rate
D the I/O rack number and starting I/O group of the adapter device
Each chassis housing an adapter device has its own addressing

method (1Ćslot, 2Ćslot, 1/2Ćslot). The addressing method specified

for a chassis is independent from that chosen for other chassis in

the remote I/O system.