Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 261

Advertising
background image

DĆ9

Block Transfer Status, Request, and Control

(4 words per block transfer request)

Register:

Bit:

Function:

Access:

Block Transfer 1

832

Block Transfer 1ĊStatus and

Control Table

read/write

0

Initiate block transfer 1
To initiate block transfer 1, set

this bit to 1. This bit remains

set until the block transfer is

complete or an error occurs.

8

Block Transfer 1Ċerror
When this bit is set to 1, an

error with block transfer 1 has

occurred.
If an error occurs with a

continuous block transfer, this

bit is set and the block

transfer is disabled.

9

Block transfer 1 complete
When a block transfer has

completed, this bit is set to 1.
Once you clear the bit, it sets

when the next transfer is

complete.
For continuous block

transfers, this bit is set to 1

when the first transfer is

complete and remains set

until you clear it via the

application program.

833

Block transfer 1's module

location and request type

read/write

0Ć4

Remote rack number to

which the module belongs.

Enter a value from 0Ć37 octal

8

Module's slot number.
Enter a value of 0 or 1.

9Ć11 The I/O group to which the

module belongs.
Enter a value from 0Ć7.

15

Block Transfer 1ĊRequest

Type
Specify a read request by

setting this bit to 1.
Specify a write request by

setting this bit to 0.

834

The number of words (length)

of Block Transfer 1.
Enter a value from 1Ć64

(words).

read/write