Initiating Scanning

Your initialization program should only initiate scanning after the

data rate has been set.
To start the PC3000 scanning the enabled racks, set bit 1 of register

768 to on (1). This bit is labeled Start Scanning in the scanner's

Variable Configurator form.
Once you initiate scanning and the scanner is in RUN mode, the

PC3000 sets the data rate as defined by the value in register 769

and starts updating I/O from the remote racks. Once scanning has

begun, the module clears the Start Scanning bit (register 768, bit 1).
If all the enabled racks are communicating, the PC3000's remote I/O

LED (green) should be on. If the serial card is present, the

7Ćsegment LEDs should be off.

16.4

Placing the Scanner in RUN Mode

When the scanner has been initiated and it is in RUN mode, the

following occurs:
D inputs are updated
D outputs are enabled
D I/O can be forced
Inputs are updated as long as the Start Scanning bit is enabled.

However, your initialization program must place the scanner module

in RUN mode so that outputs in the remote racks being scanned are

updated.
To place the scanner in RUN mode, set bit 0 of the variable

associated with register 768 to on (1). This bit is labeled Scan Mode

in the scanner's Variable Configurator form.
The Scan Mode bit is reset to off (0) whenever a STOP ALL error

occurs. For a list of STOP ALL error codes, see chapter 19.

16.5

What to Do Next

Begin creating and implementing your control programs.