Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 74

Advertising
background image

4Ć16

If you place the three blockĆtransfer modules in different racks,

however, you can blockĆtransfer to all three modules in one I/O

scan. To optimize your system layout for blockĆdata transfers, use an

arrangement similar to the following:

With this arrangement, a blockĆtransfer to each BT

module can occur in a single discrete I/O scan.

Maximum scan time

Minimum time to complete

a blockĆtransfer to all modules

= 3 discrete scans + 3 blockĆtransfers
= 3D + 3BT

= 1  (3D + 3BT)
= 3D + 3BT

Adapter

BT

Adapter

Adapter

AMX

AĆB RIO

Scanner

BT

BT

Figure 4.9 Ć System Optimized for BlockĆData Transfer

Here are some guidelines regarding program scan times:

If you are:

Your program's scan time

should be:

using blockĆtransfers

greater than the minimum time to

complete a blockĆtransfer to all

block transfer modules

not using block transfers

greater than the remote I/O scan time

4.6

AllenĆBradley Remote I/O Installation

Considerations

AllenĆBradley remote I/O equipment requires mounting, wiring and

grounding practices that may be different from AutoMax mounting,

wiring and grounding practices. Although this section highlights

some key points, refer to these standards and publications for

complete details:
D IEEE standard 518Ć1982
D Rockwell Automation Industrial Automation Wiring and

Grounding Guidelines, publication 1770Ć4.1

D Rockwell Automation Safety Guidelines for the Application,

Installation, and Maintenance of Solid State Controls, publication

SGIĆ1.1

Also, we provide recommendations for configuring adapter devices.

Refer to section 4.6.3 for specific switch setting information.