Rockwell Automation 57C570 AutoMax PC3000 User Manual User Manual

Page 187

Advertising
background image

18Ć5

See the following table for a description of the registers in the drop 0

area.

Table 18.6 ĆDescription of Registers in Drop 0 Area

Registers

Description

Registers 4 Ć 7

(Drop Status Bits)

WARNING

THE DROP 0 STATUS BITS MUST BE USED IN AN

APPLICATION PROGRAM TO INDICATE NETWORK

COMMUNICATION FAILURE. FAILURE TO OBSERVE

THIS PRECAUTION MAY RESULT IN BODILY INJURY.

WARNING

THE USER MUST PROVIDE AN EXTERNAL,

HARDWIRED EMERGENCY STOP CIRCUIT OUTSIDE

OF THE CONTROLLER CIRCUITRY. THIS CIRCUIT

MUST DISABLE THE SYSTEM IN CASE OF IMPROPER

OPERATION.

UNCONTROLLED

MACHINE

OPERATION MAY RESULT IF THIS PROCEDURE IS

NOT FOLLOWED. FAILURE TO OBSERVE THIS

PRECAUTION COULD RESULT IN BODILY INJURY.

In the master, the drop status bits indicate which slave

drops are active on the network. The drop status bit will

be equal to 1 whenever the corresponding slave drop is

actively communicating with the master.
In the slave, the drop status bits indicate which drops

represented by that slave module are active on the

network. The drop status bits will be equal to 1 when the

corresponding drop is actively communicating with the

master. If any of these bits are equal to 0, it indicates that

the drop is either not represented by that slave module

or is not communicating with the master.
In a slave module, the drop 0 status bit (register 4, bit 0)

functions as the logical AND of the status bits of all the

drops that slave module represents. The drop 0 status

bit will be equal to 1 when ALL drops represented by

that slave module are actively communicating with the

master module. If any of the drops represented by the

slave are not communicating with the master, the drop 0

status bit will be equal to 0. Therefore, the drop 0 status

bit is used to indicate whether the slave module is

communicating properly. If a drop fails, the status bit will

be off a minimum of 120 milliseconds to allow detection

by an application task.
For example, in a slave module with a drop setting of 02

and a drop depth of 3, the drop 0 status bit will be equal

to 1 if the drop status bits for drops 2, 3, and 4 are also

equal to 1 (i.e., communicating with the master). Refer to

figure 18.2. If any or all of the three drops are not

communicating with the master, the drop 0 status bit will

be equal to 0.

Advertising
This manual is related to the following products: