Rockwell Automation Publication 2099-UM001D-EN-P - December 2012

Chapter 5

Configure and Startup the Kinetix 7000 Drive System

Configure the Drive Modules

Follow these steps to configure the Kinetix 7000 drive.

1. Verify that there is no power applied to the drive and that the SERCOS

fiber-optic cables are plugged into the Tx and Rx connectors.

To verify your fiber-optic cable connections, refer to page

101

.

2. Set the base node address for the drive by setting the SERCOS Node

Address switch.

Valid node addresses are 01...99. The left hand switch sets the most
significant digit (MSD) and the right hand switch sets the least significant
digit (LSD).

Refer to the table and figure below for switch operation.

Table 48 - Node Addressing Switch Settings

Figure 63 - N ode Addressing Switch Settings

3. Cycle control power to initialize the drive.

4. Set the SERCOS communications rate using DIP switches 2 and 3.

To

Press

Increment the (MSD/LSD) node address

The plus (+) switch.

Decrement the (MSD/LSD) node address

The minus (-) switch.

IMPORTANT

When two or more drives are connected to the same SERCOS interface
module, each node address must be unique.

Refer to the node addressing examples beginning on page

108

.

IMPORTANT

The base node address setting takes effect only after the drive is
initialized.

For This Communication Rate

Set Switch 2

Set Switch 3

4 Mbps

OFF

ON

8 Mbps

ON

OFF

Decrements MSD

MSD

Increments MSD

Decrements LSD

LSD

Increments LSD