Wire the safe-off (so) connector, D in, Table 36 – Rockwell Automation 2099-BMxx Kinetix 7000 High Power Servo Drive User Manual User Manual

Page 90

Advertising
background image

90

Rockwell Automation Publication 2099-UM001D-EN-P - December 2012

Chapter 4

Connect the Kinetix 7000 Drive System

Table 36 - DC Input Power Connections

Wire the Safe-off (SO) Connector

Wire the Safe-off connections to your Kinetix 7000 drive as described in

Table 37

. See Safe-off (SO) Terminal Block Connections for more information.

Table 37 - Safe-off Connections

Kinetix 7000
Drive Cat. No.

Signal Description

Terminal(s)

Recommended Wire Size
mm

2

(AWG)

Torque
N

m (lb

in)

2099-BM06-S
2099-BM07-S
2099-BM08-S

DC+
DC-

DC+
DC-

25…2.5 (3…14)

1.8 (16)

2099-BM09-S

DC+
DC-

DC+
DC-

50…4 (1/0…12)

3.6 (32)

2099-BM10-S

DC+
DC-

DC+
DC-

70…10 (2/0…8)

15 (133)

2099-BM11-S
2099-BM12-S

DC+
DC-

DC+
DC-

100…10 (4/0…8)

12 (104)

IMPORTANT

Terminals 8 and 9 (24V+ and Common) are only used by the motion-
allowed jumper. When using the Safe-off feature, the 24V supply must
come from an external source.

Signal

Terminal

Recommended Wire Size
mm

2

(AWG)

Strip Length
mm

2

(in.)

Torque
N

m (lb

in)

FDBK2+

1

0.75 (18)
(stranded wire with ferrule)
1.5 (16)
(solid wire)

7.0 (0.275)

0.235 (2.0)

FDBK2-

2

FDBK1+

3

FDBK1-

4

ENABLE2+

5

ENABLE-

6

ENABLE1+

7

SO_24VDC

8

SO_COM

9