63

Kinetix 7000 Connector Data

Chapter 3

General Purpose I/O (GPIO Connector)

Two 24V digital outputs are user programmable. You can monitor the status the
an optional regenerative power supply. An isolated, external 24V DC power
source must be customer supplied to power the digital outputs.

Table 21 - General Purpose I/O Digital Output Specifications

The two DC current sourcing outputs default settings are Zero_Speed
(Digital_Out_1) and In_Position (Digital_Out_2). Zero_Speed is the motor at
0 rpm velocity. In_Position can be set to the commanded position by the Position
Lock Tolerance (set in Axis Properties/Limits). Default parameter selections can
also be set with an IDN function.

Figure 39 - General Purpose I/O Digital Output Diagram

Pin

Signal

Description

On Condition

Off Condition Leakage

1

Digital_Out_1

Optically isolated to 500V, current sourcing up to 75 mA

24…40V DC

<0.25 mA

2

DO_24VDC_1

24V DC power source to digital inputs (customer-supplied)

3

DO_24VDC_2

4

Digital_Out_2

Optically isolated to 500V, current sourcing up to 75 mA

24…40V DC

<0.25 mA

5

Reserved

6

1

k

Ω

0.1

μ

F

3.32

k

Ω

10

Ω

10

Ω

1

k

Ω

0.1

μ

F

3.32

k

Ω

DO_24VDC_1

Digital_Out_1

DO_24VDC_2

Digital_Out_2

Dig_Out_1

Dig_Out_2