When mounting your shunt module inside the enclosure, follow these additional
guidelines.

Metal-clad modules can be mounted anywhere in the dirty zone, but as

close to the Kinetix 7000 system as possible.

Shunt power wires can be run with motor power cables.
Keep unshielded wiring as short as possible. Keep shunt wiring as flat to

the cabinet as possible.

Separate shunt power cables from other sensitive, low voltage signal cables.
The shunt module watts dissipation must be included in the Kinetix 7000

system heat dissipation calculation for selecting an enclosure.

Figure 15 - External Shunt Resistor Inside the Enclosure

Motor Brake and Thermal Switch

The thermal switch and brake are mounted inside the motor, but how you
connect to the axis module depends on the motor series.

See Wire Motor Output Power on page

92

for wiring guidelines specific to your

drive/motor combination, and to

Interconnect Diagram Notes

on page

162

for

the interconnect diagram of your drive/motor combination.

C1

C1

VD

D3

D2

D1

VD

VD

D1

D2

Kinetix 7000

Dirty Wireway

Clean Wireway

No sensitive

equipment within

150 mm (6.0 in.)

Motor Power Cables

Very dirty connections segregated (not

in wireway)

Route 24V DC I/O
Shielded Cable

Route Encoder/Analog/Registration
Shielded Cables

Observe minimum clearance
requirements for shunt
module spacing.

Enclosure

Shunt Module

Shunt Wiring Methods:
Twisted pair in conduit (1st choice).
Shielded twisted pair (2nd choice).
Twisted pair, 2 twists per foot min.
(3rd choice).

I/O and Feedback

Cables

AC Line

Filter