Rockwell Automation Publication 2099-UM001D-EN-P - December 2012

31

Install the Kinetix 7000 Drive System

Chapter 2

Noise Zones when Using Regenerative Power Supplies (with/without a Line Filter Unit)

Observe the following guidelines when laying out a Kinetix 7000 system panel if
a regenerative power supply (8720-RPS

xxxxx) is used (see

Figure 10

), and if a

regenerative power supply and line filter unit are used (see

Figure 11

on page

32

).

Mount the regenerative power supply to the right of the drive.
The clean zone (C) is beneath and left of the Kinetix 7000 drive. This zone

includes the motor feedback, auxiliary feedback and registration signals
from the IOD connector (grey wireway).

The dirty zone (D) is to the right of the Kinetix 7000 drive. This zone

includes the motor power, GPIO, GPR, SO, and IOD connections (black
wireway).

The very dirty zone (VD) includes both the 8720MC-RPS DC output to

the Kinetix 7000 drive and the fuses, contactors, circuit breakers, and AC
line input to the EMC line filter to the right of the 8720MC-RPS.
Shielded cable is required only if the very dirty cables enter a wireway.

The SERCOS fiber-optic cables are immune to electrical noise.

Figure 10 - Establishing Noise Zones (Regenerative Power Supply)

C1

C1

D3

D2

R E G E N E R A T IV E P O W E R S U P P LY

REGENERATIVE POWER SUPPLY

8720

8720

MC

MC

RST

PRG

ENT

READY

READY

FAULT

FAULT

PROGRAM

PROGRAM

kW

kW

V

A

VD

VD

D2

D1

Route Encoder/Analog/Registration
Shielded Cable

Shielded Cable or

Conduit

Clean Wireway (Cx)

No sensitive

equipment within

150 mm (6.0 in.)

Dirty Wireway (Dx)

Shield Clamps
(beneath cover)

Motor Power
Shielded Cable

8720MC

Line Reactor

Registration I/O

24V DC

Kinetix 7000 Drive

24V DC I/O
Shielded Cable

GPIO, GPR, and SO Cables

Dirty Wireway (Dx)

24V DC

Power

Supply

DC Bus

2 m (78.7 in.)

Keep very dirty (VD) connections as short as

possible and segregated (not in wireway)

AC

Line

Filter

Magnetic

Contactor

Line

Fuses

Circuit

Breaker

8720MC-RPS065BM-HV2
Regenerative Power Supply

Harmonic

Filter

Varistor

Encoder Feedback