Troubleshoot the Kinetix 7000 Drive System

Chapter 6

Status Indicators

Table 51 - Drive Status Indicator

Table 52 - Comm Status Indicator

Table 53 - Bus Status Indicator

Drive Status LED

Status

Potential Cause

Possible Resolution

Off

Normal, no faults

N/A

N/A

Steady Red

Drive faulted

Seven-segment status indicator displays error code.

See the Error Codes on page

138

section and continue

troubleshooting.

Comm Status LED

Status

Potential Cause

Possible Resolution

Off

No communication

(1)

Loose fiber-optic connection.

Verify proper fiber-optic cable connection.

Broken fiber-optic cable.

Replace fiber-optic cable.

Receive fiber-optic cable connected to SERCOS
transmit connector and vice versa.

Check proper SERCOS fiber-optic cable connections.

Flashing Green

Establishing communication

System is still in the process of establishing SERCOS
communication.

Wait for steady green indicator.

Node address setting on the drive module does not
match SERCOS controller configuration.

Verify proper node switch setting.

Steady Green

Communication ready

No faults or failures.

N/A

(1) Refer to Fiber-optic Cable Installation and Handling Instructions, publication

2090-IN010

, for more information.

Bus Status LED

Status

Condition

Off

Bus power not present.

Normal when bus power is not applied.
Fault exists, see the Interpret Error Codes and Status Indicators beginning on page

138

.

Bus power is present in follower drive.

Follower drive is not configured as Common Bus Follow in RSLogix 5000 software.
After DC bus voltage is applied, a 2.50 second delay occurs before the indicator begins flashing

green.
This is normal operation and provides the common bus leader time to complete precharge.

Alternating Red-Green

Bus power not present.
24V DC control power is present.

Normal when bus power is not applied. Verify 460V AC connections.
Fault exists, see the Interpret Error Codes and Status Indicators beginning on page

138

.

Flashing Green

Bus power is present, axis disabled.
No faults or failures.

Normal when:
24V is not applied to Hardware Enable Input (IOD-2).
MSO instruction is not commanded in RSLogix 5000 software.

Steady Green

Bus power is present, axis enabled.
No faults or failures.

Normal when:
24V is applied to Hardware Enable Input (IOD-2).
MSO instruction is commanded in RSLogix 5000 software.