Customer-supplied 24V DC Power Supply Notes

The contact connected to GPR1+ and GPR1- is rated 2 Amps inductive

@ 250V AC/30V DC maximum.

MPx motors with a brake have various coil current requirements. Refer to

the Kinetix Motion Control Selection Guide, publication

GMC-SG001

for coil current requirements.

For motors that utilize above 2 Amp coil current it is recommended that a

customer-supplied external device, such as an interposing relay, be used
between the drive and motor. See

Figure 82

below.

A customer-supplied diode or metal oxide varistor (MOV) is

recommended for use with an interposing relay to prevent an electrical arc
that may occur before the brake coil power dissipates. Use of an MOV can
also reduce the amount of time required to mechanically engage the brake.
See

Figure 82

below.

Figure 82 - Customer-supplied 24V DC Power Supply Wiring Example

BR+

BR-

A

C

3
2
4
1

GPR1-
GPR1+
COM
24VDC

24VDC

Supply

+ -

C1

C1

*Dashed lines

denote customer

supplied components.

Kinetix 7000

Drive

MPL Motor