CE Requirements - System with LIM

To meet CE requirements when your Kinetix 7000 system includes the line
interface module (LIM), follow all the requirements as stated in CE
Requirements - System without LIM
on page

19

and these additional

requirements that also apply to the AC line filter:

Install the LIM, 2094-XL75S-Cx or 2094-BL50/75S, and line filter

(2090-XXLF-TC

xxx) as close to the Kinetix 7000 drive as possible.

CE Requirements - System with DC Common Bus through 8720MC-RPS

To meet CE requirements when your Kinetix 7000 system includes a common
DC bus with an 8720MC-RPS, follow all the requirements as stated in the CE
Requirements - System without LIM
on page

19

, the recommended installation

and wiring in the 8720MC Regenerative Power Supply Reference Manual,
publication

8720MC-RM001

, and these additional requirements:

Install a three-phase line filter on the AC input power line of the RPS as

indicated in Interconnect Diagrams beginning on page

161

.

Install a single-phase line filter when attaching an AC line input to the

RPS MC1/2 circuit as indicated in the Interconnect Diagrams beginning
on page

161

.

IMPORTANT

The full rated current on the AC input line should not exceed that of the line
interface module.

Catalog numbers 2094-XL75S-Cx or 2094-BL50S for 2099-BM06-S and
2099-BM07-S Kinetix 7000 drives, or 2094-BL75S for 2099-BM08-S Kinetix
7000 drives.

IMPORTANT

CE requires use of a grounded secondary or source with a 2099-BMxx-S
drive.

Never use a LIM in an ungrounded input, due to the potential for high line-
to-neutral voltages damaging components within the line filter.