C - upgrade firmware, Before you begin, Appendix c – Rockwell Automation 2099-BMxx Kinetix 7000 High Power Servo Drive User Manual User Manual

Page 179: Upgrade firmware, Appendix

Advertising
background image

Rockwell Automation Publication 2099-UM001D-EN-P - December 2012

179

Appendix

C

Upgrade Firmware

This appendix provides procedures for using ControlFlash utility to upgrade the
firmware in a Kinetix 7000 drive.

Before You Begin

Upgrading the firmware of a Kinetix 7000 servo drive using ControlFlash
involves entering the name of the target device, locating the SERCOS interface
module and Kinetix 7000 servo drive to be flashed, finding the existing new
firmware levels, and flashing the drive firmware.

Before you begin this procedure, make sure you have the following.

Topic

Page

Before You Begin

179

Upgrade Firmware

180

Description

Catalog Numbers

Version

RSLogix 5000

Software

9324-RLD300NE

15.0 or later

RSLinx Software

0355-RSLETENE

2.50.00 or later

ControlFlash Kit

(1)

(1) For ControlFlash information not specific to the Kinetix 7000 drive family, refer to the ControlFlash Firmware Upgrade Kit Quick

Start, publication

1756-QS105

.

N/A

4.00.09 or later

Firmware for Logix SERCOS interface module or
PCI card

1756-MxxSE

15.32 or later

1756-L60M03SE

15.4 or later

1768-M04SE

15.35 or later

1784-PM16SE

15.33 or later

Firmware upgrade file for Kinetix 7000

(2),(3)

(2) Contact Rockwell Automation Technical Support at (440) 646-5800 for firmware upgrade files and assistance.

(3) Go to

http://support.rockwellautomation.com/firmware.asp

for firmware upgrades.